FLUKE 393FC AC DC Clamp Meter

66,820.00

The Fluke 393FC CAT III 1500 V True-rms Solar Clamp Meter with iFlex is designed for solar photovoltaic (PV) installation technicians & professionals

Categories: ,

Description

Key features

  • Fluke 393FC Measure safely with CAT III 1500 V rated clamp meter
  • Thin jaw for access to cables in crowded combiner boxes
  • Sturdy IP54 rated for outdoor use and solar installation
  • Work efficiently with dc power measurement, audio polarity and visual continuity

The Fluke 393 FC CAT III 1500 V True-rms Solar Clamp Meter with iFlex is designed for solar photovoltaic (PV) installation technicians and maintenance professionals who work in high voltage DC environments: PV arrays, wind power, electric railways, data centers battery banks for uninterruptible power supplies. The clamp meter will measure up to 1500 V DC and 1000 V AC with test leads, and up to 999.9 A DC or AC through the clamp jaw. The included iFlex flexible current probe extends AC current measurements up to 2500 A. The 393 has a thin jaw, giving you access to cables in crowded combiner boxes. Plus, the test leads are designed with your work in mind, and are also rated to CAT III 1500 V DC.

Key functions of the solar clamp meter:

  • IP54 rated, ideal for work outdoors including PV panel testing
  • DC power measurement, showing readings in kVA
  • Audio Polarity indicator helps prevent accidental miswires
  • Visual Continuity provides a bright green light in the display, ideal when working in dark and noisy environments
  • Logging and reporting of test results via Fluke Connect software
  • When measuring ac current the included iFlex flexible current probe gives you unparalleled access to cable is tight spaces.  The iFlex probe can be twisted through extremely small spaces and provide accurate current measur

    Specifications: Fluke 393 FC Solar Clamp Meter CAT III 1500 V

    Specifications:
    General
    Maximum voltage between any Terminal and Earth Ground
    AC 1000 V
    DC 1500 V
    Batteries 2 AA IEC LR6 alkaline
    Display Dual display with backlight
    Automatic Power Off 20 minutes
    Electrical
    Accuracy
    Accuracy is specified for 1 year after calibration, at operating temperatures of 18 °C to 28 °C, relative humidity at 0 % to 75 %. Accuracy specifications take the form of: ±([% of Reading] + [Number of Least Significant Digits]).
    Temperature Coefficients Add 0.1 x specified accuracy for each °C > 28 °C or < 18 °C
    AC Current: Jaw
    Range 999.9 A
    Resolution 0.1 A
    Accuracy 2 % + 5 digits (10 Hz to 100 Hz)
    2.5 % + 5 digits (100 Hz to 500 Hz)
    Crest Factor (50/60 Hz) 2.5 @600.0 A
    3.0 @500.0 A
    1.42 @999.9 A
    Add 2 % for C.F. >2
    AC Current: Flexible Current Probe
    Range 999.9 A
    2500 A
    Resolution 0.1 A (≤999.9 A)
    1 A (≤2500 A)
    Accuracy 3 % RD + 5 digits (10 Hz to 500 Hz)
    Crest Factor (50/60Hz) 2.5 @1400 A
    3.0 @1100 A
    1.42@2500 A
    Add 2 % for C.F. >2
    Position Sensitivity
    NEC symbol
    Distance from Optimum i2500-10 Flex i2500-18 Flex Error
    A 0.5 in (12.7 mm) 1.4 in (35.6 mm) ±0.5 %
    B 0.8 in (20.3 mm) 2.0 in (50.8 mm) ±1.0 %
    C 1.4 in (35.6 mm) 2.5 in (63.5 mm) ±2.0 %
    Measurement uncertainty assumes centralized primary conductor at optimum position, no external electrical or magnetic field, and within operating temperature range.
    DC Current
    Range 999.9 A
    Resolution 0.1 A
    Accuracy 2 % RD + 5 digits[1]
    [1] When using the ZERO (B) function to compensate for offsets.
    AC Voltage
    Range 600.0 V
    1000 V
    Resolution 0.1 V (≤600.0 V)
    1 V (≤1000 V)
    Accuracy 1 % RD + 5 digits (20 Hz to 500 Hz)
    DC Voltage
    Range 600.0 V
    1500 V
    Resolution 0.1 V (≤600.0 V)
    1 V (≤1500 V)
    Accuracy 1 % RD + 5 digits
    mV dc
    Range 500.0 mV
    Resolution 0.1 mV
    Accuracy 1 % RD + 5 digits
    Amps Frequency: Jaw
    Range 5.0 Hz to 500.0 Hz
    Resolution 0.1 Hz
    Accuracy 0.5 % RD + 5 digits
    Trigger Level 5 Hz to 10 Hz, ≥10 A
    10 Hz to 100 Hz, ≥5 A
    100 Hz to 500 Hz, ≥10 A
    Amps Frequency: Flexible Current Probe
    Range 5.0 Hz to 500.0 Hz
    Resolution 0.1 Hz
    Accuracy 0.5 % RD + 5 digits
    Trigger Level 5 Hz to 20 Hz, ≥25 A
    20 Hz to 100 Hz, ≥20 A
    100 Hz to 500 Hz, ≥25 A
    Voltage Frequency
    Range 5.0 Hz to 500.0 Hz
    Resolution 0.1 Hz
    Accuracy 0.5 % RD + 5 digits
    Trigger Level 5 Hz to 20 Hz, ≥5 V
    20 Hz to 100 Hz, ≥5 V
    100 Hz to 500 Hz, ≥10 V
    DC Power
    Range 600.0 kVA (600.0 V dc range)
    1500 kVA (1500 V dc range)
    Resolution 0.1 kVA
    1 kVA
    Accuracy 2 % RD + 2.0 kVA
    2 % RD + 20 kVA
    Resistance
    Range 600.0 Ω
    6000 Ω
    60.00 kΩ
    Resolution 0.1 Ω (≤600.0 Ω)
    1 Ω (≤6000 Ω)
    0.01 kΩ (≤60.00 kΩ)
    Accuracy 1 % RD + 5 digits
    Capacitance
    Range 100.0 μF
    1000 μF
    Resolution 0.1 μF (≤100.0 μF)
    1 μF (≤1000 μF)
    Accuracy 1 % RD + 5 digits
    Inrush Trigger Level 5 A
    Mechanical
    Size (L x W x H) 281 mm x 84 mm x 49 mm
    Weight (with batteries) 520 g
    Jaw Opening 34 mm
    Flexible Current Probe Diameter 7.5 mm
    Flexible Current Probe Cable Length
    (head to electronics connector) 1.8 m
    Environmental
    Operating Temperature -10 °C to 50 °C
    Storage Temperature -40 °C to 60 °C
    Operating Humidity Non condensing (<10°C)
    ≤90 % RH (at 10 °C to 30 °C)
    ≤75 % RH (at 30 °C to 40 °C)
    ≤45 % RH (at 40 °C to 50 °C)
    Operating Altitude 2000 m
    Storage Altitude 12 000 m
    Ingress Protection (IP) Rating IEC 60529: IP54 non-operating
    Electromagnetic Compatibility (EMC)
    International IEC 61326-1: Portable, Electromagnetic Environment, IEC 61326-2-2 CISPR 11: Group 1, Class A
    Group 1: Equipment has intentionally generated and/or uses conductively-coupled radio frequency energy that is necessary for the internal function of the equipment itself.
    Class A: Equipment is suitable for use in all establishments other than domestic and those directly connected to a low-voltage power supply network that supplies buildings used for domestic purposes. There may be potential difficulties in ensuring electromagnetic compatibility in other environments due to conducted and radiated disturbances.
    Caution: This equipment is not intended for use in residential environments and may not provide adequate protection to radio reception in such environments.
    Korea (KCC) Class A equipment (Industrial Broadcast & Communications Equipment)
    Class A: Equipment meets requirements for industrial electromagnetic wave equipment and the seller or user should take notice of it. This equipment is intended for use in business environments and not to be used in homes.
    USA (FCC) 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103.
    Safety
    General IEC 61010-1, Pollution Degree 2
    Measurement IEC 61010-2-032: CAT III 1500 V / CAT IV 600 V
    IEC 61010-2-033: CAT III 1500 V / CAT IV 600 V
    Wireless Radio
    Radio frequency certification FCC ID: T68-FBLE, IC: 6627A-FBLE
    Wireless Radio Frequency Range 2400 MHz to 2483.5 MHz
    Output Power <100 mW

    ements.